Can I run a new neutral wire to repair a broken circuit?How can I upgrade a 3 wire appliance receptacle to a 4 wire receptacle?How can I find an open neutral?Contractor cut wire in wall - all still works fine - is this dangerous?Need help troubleshooting dead outletsOutlet w/3 neutrals, 3 hots, 1 ground?Can I connect to a separate neutral (white) wire for my switch/outlet combination?Dead receptacle in the basementMultiple outlets not workingHow can I provide neutral wires for my smart switches?Neutral wire going into panel has ~120 volts on it
Why doesn't using multiple commands with a || or && conditional work?
Do scales need to be in alphabetical order?
Why is it a bad idea to hire a hitman to eliminate most corrupt politicians?
Why didn't Miles's spider sense work before?
Probability that a draw from a normal distribution is some number greater than another draw from the same distribution
Why would the Red Woman birth a shadow if she worshipped the Lord of the Light?
What about the virus in 12 Monkeys?
Venezuelan girlfriend wants to travel the USA to be with me. What is the process?
How can saying a song's name be a copyright violation?
Bullying boss launched a smear campaign and made me unemployable
Is there an expression that means doing something right before you will need it rather than doing it in case you might need it?
How writing a dominant 7 sus4 chord in RNA ( Vsus7 chord in the 1st inversion)
Why is this clock signal connected to a capacitor to gnd?
How badly should I try to prevent a user from XSSing themselves?
Forming a German sentence with/without the verb at the end
Is "remove commented out code" correct English?
How can I deal with my CEO asking me to hire someone with a higher salary than me, a co-founder?
Madden-Julian Oscillation (MJO) - How to interpret the index?
How to tell a function to use the default argument values?
Is it logically or scientifically possible to artificially send energy to the body?
How to show a landlord what we have in savings?
Is it acceptable for a professor to tell male students to not think that they are smarter than female students?
What exploit Are these user agents trying to use?
Why do bosons tend to occupy the same state?
Can I run a new neutral wire to repair a broken circuit?
How can I upgrade a 3 wire appliance receptacle to a 4 wire receptacle?How can I find an open neutral?Contractor cut wire in wall - all still works fine - is this dangerous?Need help troubleshooting dead outletsOutlet w/3 neutrals, 3 hots, 1 ground?Can I connect to a separate neutral (white) wire for my switch/outlet combination?Dead receptacle in the basementMultiple outlets not workingHow can I provide neutral wires for my smart switches?Neutral wire going into panel has ~120 volts on it
Recently one wall of outlets quit working. Testing shows the hots are all good and the grounds are all good but the neutrals are all dead. They are all connected to each other but somewhere have lost the connection to the panel.
Can I add a neutral from another nearby outlet which will make these outlets work without tearing up the walls to find where the neutral has become disconnected?
electrical wiring
New contributor
add a comment |
Recently one wall of outlets quit working. Testing shows the hots are all good and the grounds are all good but the neutrals are all dead. They are all connected to each other but somewhere have lost the connection to the panel.
Can I add a neutral from another nearby outlet which will make these outlets work without tearing up the walls to find where the neutral has become disconnected?
electrical wiring
New contributor
add a comment |
Recently one wall of outlets quit working. Testing shows the hots are all good and the grounds are all good but the neutrals are all dead. They are all connected to each other but somewhere have lost the connection to the panel.
Can I add a neutral from another nearby outlet which will make these outlets work without tearing up the walls to find where the neutral has become disconnected?
electrical wiring
New contributor
Recently one wall of outlets quit working. Testing shows the hots are all good and the grounds are all good but the neutrals are all dead. They are all connected to each other but somewhere have lost the connection to the panel.
Can I add a neutral from another nearby outlet which will make these outlets work without tearing up the walls to find where the neutral has become disconnected?
electrical wiring
electrical wiring
New contributor
New contributor
edited 4 hours ago
isherwood
51.1k460130
51.1k460130
New contributor
asked 4 hours ago
James WolfJames Wolf
161
161
New contributor
New contributor
add a comment |
add a comment |
2 Answers
2
active
oldest
votes
No, you cannot do this. Assuming the nearby outlet you want to borrow neutral from is on a different circuit, you will be overloading its neutral. Even if it is the same circuit, it's very bad practice to leave broken wiring energized without fixing it -- what if it moves a little and reconnects just enough to arc? Then your house is on fire.
However, fixing this properly probably isn't as much work as you think. You most likely will not need to tear up your walls. Unless you recently drove a nail through a wire, the wire inside the walls usually doesn't just break. Rather, where things go wrong is at the outlets themselves. The so-called "backstab" outlets are especially prone to having the wires come lose over time. So the fix for this will involve pulling out each outlet in turn, making sure all screws, wirenuts, etc are tight, and ideally replacing any backstabs in the circuit. Most likely you'll find one of the outlets had the white wire come loose, and when you tighten it, everything starts working again.
2
The failure is usually at the last working outlet or the first non working outlet. In rare cases where nothing on the circuit works it can be in the panel.
– Ed Beal
3 hours ago
If a breaker was tripping you might think about damage to the wire between boxes more (drove a nail into a wire, etc) but it would be hard for wire damage to result in only a broken neutral. Find all the outlets that do work and start checking them starting with the closest one to the broken outlet.
– JPhi1618
3 hours ago
That's true; most likely OP can get away with only checking only two outlets IF they know what order the circuit is wired in. However, I still recommend opening them all up since most likely they were all wired at the same time with the same techniques, and if one failed, the others might not be far behind. And that way you don't need to know the circuit order, which most likely OP doesn't.
– Nate Strickland
2 hours ago
add a comment |
Absolutely not. That sort of thinking works with safety ground, which does not ever carry current, except during a fault condition (and we hope there aren't 2 independent fault conditions occurring at once).
However, current flows in loops. Neutral is the normal "return half" of the loop, and it needs to be dedicated to this circuit. In fact, neutrals don't have fuses and rely on the circuit breaker on the hot side to protect the neutral. You can't have two circuits sharing a neutral, or you get this!
But there's another problem. This is AC power. It reverses polarity 100/120 times a second, which throws electro-magnetic force into everything around the wires. That's why transformers work. To keep that from causing a lot of problems, we require that all the current that goes out one wire comes back on another in the same cable or conduit. Among the wires, currents are equal and opposite, so their electro-magnetic forces cancel each other out.
Now, borrowing a neutral means current is now making a big loop - "out" (really, it's AC) this circuit's "hot" wire and returning via another circuit's "neutral" wire. That will throw EMF on both circuits, causing all sorts of mischief - eddy current heating, wire vibration leading to noise and metal fatigue leading to cracking and spot heating, etc. Nope.
Because of this, all practical wiring is done on a physical "tree" topology -- a branch may "split", but it may never "loop back" onto itself or another branch (except in one particular way, and even then, only in the UK where this is officially sanctioned).
Now, it can be hard to see when you're not practiced in a field. But this is most likely an easy problem. Wire breaks inside walls are rare. Wire problems are almost always at terminations of the cable run... And by definition, this must occur at either the last working outlet or the first failed outlet in the sequence.
As Nate discusses in his answer, backstab connections are the usual culprit. You're best changing it to a screw connection, but current Code advises using an $80 torque screwdriver, because "too loose" is more of a problem than "too tight".
If it's at the service panel, the neutral may go to a neutral bar, or a GFCI or AFCI breaker. Torque matters here too.
Lastly, if this diagnosis is given you by a 3-light tester, know that some of us call it a "Magic 8-ball" tester. It is made as a pass-fail device for new wiring e.g. During new construction. When troubleshooting old existing work, the legends can be wrong to the point of whimsical. The lights are useful; they save you the trouble of making 3 measurements with a neon tester.
add a comment |
Your Answer
StackExchange.ready(function()
var channelOptions =
tags: "".split(" "),
id: "73"
;
initTagRenderer("".split(" "), "".split(" "), channelOptions);
StackExchange.using("externalEditor", function()
// Have to fire editor after snippets, if snippets enabled
if (StackExchange.settings.snippets.snippetsEnabled)
StackExchange.using("snippets", function()
createEditor();
);
else
createEditor();
);
function createEditor()
StackExchange.prepareEditor(
heartbeatType: 'answer',
autoActivateHeartbeat: false,
convertImagesToLinks: false,
noModals: true,
showLowRepImageUploadWarning: true,
reputationToPostImages: null,
bindNavPrevention: true,
postfix: "",
imageUploader:
brandingHtml: "Powered by u003ca class="icon-imgur-white" href="https://imgur.com/"u003eu003c/au003e",
contentPolicyHtml: "User contributions licensed under u003ca href="https://creativecommons.org/licenses/by-sa/3.0/"u003ecc by-sa 3.0 with attribution requiredu003c/au003e u003ca href="https://stackoverflow.com/legal/content-policy"u003e(content policy)u003c/au003e",
allowUrls: true
,
noCode: true, onDemand: true,
discardSelector: ".discard-answer"
,immediatelyShowMarkdownHelp:true
);
);
James Wolf is a new contributor. Be nice, and check out our Code of Conduct.
Sign up or log in
StackExchange.ready(function ()
StackExchange.helpers.onClickDraftSave('#login-link');
);
Sign up using Google
Sign up using Facebook
Sign up using Email and Password
Post as a guest
Required, but never shown
StackExchange.ready(
function ()
StackExchange.openid.initPostLogin('.new-post-login', 'https%3a%2f%2fdiy.stackexchange.com%2fquestions%2f161304%2fcan-i-run-a-new-neutral-wire-to-repair-a-broken-circuit%23new-answer', 'question_page');
);
Post as a guest
Required, but never shown
2 Answers
2
active
oldest
votes
2 Answers
2
active
oldest
votes
active
oldest
votes
active
oldest
votes
No, you cannot do this. Assuming the nearby outlet you want to borrow neutral from is on a different circuit, you will be overloading its neutral. Even if it is the same circuit, it's very bad practice to leave broken wiring energized without fixing it -- what if it moves a little and reconnects just enough to arc? Then your house is on fire.
However, fixing this properly probably isn't as much work as you think. You most likely will not need to tear up your walls. Unless you recently drove a nail through a wire, the wire inside the walls usually doesn't just break. Rather, where things go wrong is at the outlets themselves. The so-called "backstab" outlets are especially prone to having the wires come lose over time. So the fix for this will involve pulling out each outlet in turn, making sure all screws, wirenuts, etc are tight, and ideally replacing any backstabs in the circuit. Most likely you'll find one of the outlets had the white wire come loose, and when you tighten it, everything starts working again.
2
The failure is usually at the last working outlet or the first non working outlet. In rare cases where nothing on the circuit works it can be in the panel.
– Ed Beal
3 hours ago
If a breaker was tripping you might think about damage to the wire between boxes more (drove a nail into a wire, etc) but it would be hard for wire damage to result in only a broken neutral. Find all the outlets that do work and start checking them starting with the closest one to the broken outlet.
– JPhi1618
3 hours ago
That's true; most likely OP can get away with only checking only two outlets IF they know what order the circuit is wired in. However, I still recommend opening them all up since most likely they were all wired at the same time with the same techniques, and if one failed, the others might not be far behind. And that way you don't need to know the circuit order, which most likely OP doesn't.
– Nate Strickland
2 hours ago
add a comment |
No, you cannot do this. Assuming the nearby outlet you want to borrow neutral from is on a different circuit, you will be overloading its neutral. Even if it is the same circuit, it's very bad practice to leave broken wiring energized without fixing it -- what if it moves a little and reconnects just enough to arc? Then your house is on fire.
However, fixing this properly probably isn't as much work as you think. You most likely will not need to tear up your walls. Unless you recently drove a nail through a wire, the wire inside the walls usually doesn't just break. Rather, where things go wrong is at the outlets themselves. The so-called "backstab" outlets are especially prone to having the wires come lose over time. So the fix for this will involve pulling out each outlet in turn, making sure all screws, wirenuts, etc are tight, and ideally replacing any backstabs in the circuit. Most likely you'll find one of the outlets had the white wire come loose, and when you tighten it, everything starts working again.
2
The failure is usually at the last working outlet or the first non working outlet. In rare cases where nothing on the circuit works it can be in the panel.
– Ed Beal
3 hours ago
If a breaker was tripping you might think about damage to the wire between boxes more (drove a nail into a wire, etc) but it would be hard for wire damage to result in only a broken neutral. Find all the outlets that do work and start checking them starting with the closest one to the broken outlet.
– JPhi1618
3 hours ago
That's true; most likely OP can get away with only checking only two outlets IF they know what order the circuit is wired in. However, I still recommend opening them all up since most likely they were all wired at the same time with the same techniques, and if one failed, the others might not be far behind. And that way you don't need to know the circuit order, which most likely OP doesn't.
– Nate Strickland
2 hours ago
add a comment |
No, you cannot do this. Assuming the nearby outlet you want to borrow neutral from is on a different circuit, you will be overloading its neutral. Even if it is the same circuit, it's very bad practice to leave broken wiring energized without fixing it -- what if it moves a little and reconnects just enough to arc? Then your house is on fire.
However, fixing this properly probably isn't as much work as you think. You most likely will not need to tear up your walls. Unless you recently drove a nail through a wire, the wire inside the walls usually doesn't just break. Rather, where things go wrong is at the outlets themselves. The so-called "backstab" outlets are especially prone to having the wires come lose over time. So the fix for this will involve pulling out each outlet in turn, making sure all screws, wirenuts, etc are tight, and ideally replacing any backstabs in the circuit. Most likely you'll find one of the outlets had the white wire come loose, and when you tighten it, everything starts working again.
No, you cannot do this. Assuming the nearby outlet you want to borrow neutral from is on a different circuit, you will be overloading its neutral. Even if it is the same circuit, it's very bad practice to leave broken wiring energized without fixing it -- what if it moves a little and reconnects just enough to arc? Then your house is on fire.
However, fixing this properly probably isn't as much work as you think. You most likely will not need to tear up your walls. Unless you recently drove a nail through a wire, the wire inside the walls usually doesn't just break. Rather, where things go wrong is at the outlets themselves. The so-called "backstab" outlets are especially prone to having the wires come lose over time. So the fix for this will involve pulling out each outlet in turn, making sure all screws, wirenuts, etc are tight, and ideally replacing any backstabs in the circuit. Most likely you'll find one of the outlets had the white wire come loose, and when you tighten it, everything starts working again.
answered 4 hours ago
Nate StricklandNate Strickland
2767
2767
2
The failure is usually at the last working outlet or the first non working outlet. In rare cases where nothing on the circuit works it can be in the panel.
– Ed Beal
3 hours ago
If a breaker was tripping you might think about damage to the wire between boxes more (drove a nail into a wire, etc) but it would be hard for wire damage to result in only a broken neutral. Find all the outlets that do work and start checking them starting with the closest one to the broken outlet.
– JPhi1618
3 hours ago
That's true; most likely OP can get away with only checking only two outlets IF they know what order the circuit is wired in. However, I still recommend opening them all up since most likely they were all wired at the same time with the same techniques, and if one failed, the others might not be far behind. And that way you don't need to know the circuit order, which most likely OP doesn't.
– Nate Strickland
2 hours ago
add a comment |
2
The failure is usually at the last working outlet or the first non working outlet. In rare cases where nothing on the circuit works it can be in the panel.
– Ed Beal
3 hours ago
If a breaker was tripping you might think about damage to the wire between boxes more (drove a nail into a wire, etc) but it would be hard for wire damage to result in only a broken neutral. Find all the outlets that do work and start checking them starting with the closest one to the broken outlet.
– JPhi1618
3 hours ago
That's true; most likely OP can get away with only checking only two outlets IF they know what order the circuit is wired in. However, I still recommend opening them all up since most likely they were all wired at the same time with the same techniques, and if one failed, the others might not be far behind. And that way you don't need to know the circuit order, which most likely OP doesn't.
– Nate Strickland
2 hours ago
2
2
The failure is usually at the last working outlet or the first non working outlet. In rare cases where nothing on the circuit works it can be in the panel.
– Ed Beal
3 hours ago
The failure is usually at the last working outlet or the first non working outlet. In rare cases where nothing on the circuit works it can be in the panel.
– Ed Beal
3 hours ago
If a breaker was tripping you might think about damage to the wire between boxes more (drove a nail into a wire, etc) but it would be hard for wire damage to result in only a broken neutral. Find all the outlets that do work and start checking them starting with the closest one to the broken outlet.
– JPhi1618
3 hours ago
If a breaker was tripping you might think about damage to the wire between boxes more (drove a nail into a wire, etc) but it would be hard for wire damage to result in only a broken neutral. Find all the outlets that do work and start checking them starting with the closest one to the broken outlet.
– JPhi1618
3 hours ago
That's true; most likely OP can get away with only checking only two outlets IF they know what order the circuit is wired in. However, I still recommend opening them all up since most likely they were all wired at the same time with the same techniques, and if one failed, the others might not be far behind. And that way you don't need to know the circuit order, which most likely OP doesn't.
– Nate Strickland
2 hours ago
That's true; most likely OP can get away with only checking only two outlets IF they know what order the circuit is wired in. However, I still recommend opening them all up since most likely they were all wired at the same time with the same techniques, and if one failed, the others might not be far behind. And that way you don't need to know the circuit order, which most likely OP doesn't.
– Nate Strickland
2 hours ago
add a comment |
Absolutely not. That sort of thinking works with safety ground, which does not ever carry current, except during a fault condition (and we hope there aren't 2 independent fault conditions occurring at once).
However, current flows in loops. Neutral is the normal "return half" of the loop, and it needs to be dedicated to this circuit. In fact, neutrals don't have fuses and rely on the circuit breaker on the hot side to protect the neutral. You can't have two circuits sharing a neutral, or you get this!
But there's another problem. This is AC power. It reverses polarity 100/120 times a second, which throws electro-magnetic force into everything around the wires. That's why transformers work. To keep that from causing a lot of problems, we require that all the current that goes out one wire comes back on another in the same cable or conduit. Among the wires, currents are equal and opposite, so their electro-magnetic forces cancel each other out.
Now, borrowing a neutral means current is now making a big loop - "out" (really, it's AC) this circuit's "hot" wire and returning via another circuit's "neutral" wire. That will throw EMF on both circuits, causing all sorts of mischief - eddy current heating, wire vibration leading to noise and metal fatigue leading to cracking and spot heating, etc. Nope.
Because of this, all practical wiring is done on a physical "tree" topology -- a branch may "split", but it may never "loop back" onto itself or another branch (except in one particular way, and even then, only in the UK where this is officially sanctioned).
Now, it can be hard to see when you're not practiced in a field. But this is most likely an easy problem. Wire breaks inside walls are rare. Wire problems are almost always at terminations of the cable run... And by definition, this must occur at either the last working outlet or the first failed outlet in the sequence.
As Nate discusses in his answer, backstab connections are the usual culprit. You're best changing it to a screw connection, but current Code advises using an $80 torque screwdriver, because "too loose" is more of a problem than "too tight".
If it's at the service panel, the neutral may go to a neutral bar, or a GFCI or AFCI breaker. Torque matters here too.
Lastly, if this diagnosis is given you by a 3-light tester, know that some of us call it a "Magic 8-ball" tester. It is made as a pass-fail device for new wiring e.g. During new construction. When troubleshooting old existing work, the legends can be wrong to the point of whimsical. The lights are useful; they save you the trouble of making 3 measurements with a neon tester.
add a comment |
Absolutely not. That sort of thinking works with safety ground, which does not ever carry current, except during a fault condition (and we hope there aren't 2 independent fault conditions occurring at once).
However, current flows in loops. Neutral is the normal "return half" of the loop, and it needs to be dedicated to this circuit. In fact, neutrals don't have fuses and rely on the circuit breaker on the hot side to protect the neutral. You can't have two circuits sharing a neutral, or you get this!
But there's another problem. This is AC power. It reverses polarity 100/120 times a second, which throws electro-magnetic force into everything around the wires. That's why transformers work. To keep that from causing a lot of problems, we require that all the current that goes out one wire comes back on another in the same cable or conduit. Among the wires, currents are equal and opposite, so their electro-magnetic forces cancel each other out.
Now, borrowing a neutral means current is now making a big loop - "out" (really, it's AC) this circuit's "hot" wire and returning via another circuit's "neutral" wire. That will throw EMF on both circuits, causing all sorts of mischief - eddy current heating, wire vibration leading to noise and metal fatigue leading to cracking and spot heating, etc. Nope.
Because of this, all practical wiring is done on a physical "tree" topology -- a branch may "split", but it may never "loop back" onto itself or another branch (except in one particular way, and even then, only in the UK where this is officially sanctioned).
Now, it can be hard to see when you're not practiced in a field. But this is most likely an easy problem. Wire breaks inside walls are rare. Wire problems are almost always at terminations of the cable run... And by definition, this must occur at either the last working outlet or the first failed outlet in the sequence.
As Nate discusses in his answer, backstab connections are the usual culprit. You're best changing it to a screw connection, but current Code advises using an $80 torque screwdriver, because "too loose" is more of a problem than "too tight".
If it's at the service panel, the neutral may go to a neutral bar, or a GFCI or AFCI breaker. Torque matters here too.
Lastly, if this diagnosis is given you by a 3-light tester, know that some of us call it a "Magic 8-ball" tester. It is made as a pass-fail device for new wiring e.g. During new construction. When troubleshooting old existing work, the legends can be wrong to the point of whimsical. The lights are useful; they save you the trouble of making 3 measurements with a neon tester.
add a comment |
Absolutely not. That sort of thinking works with safety ground, which does not ever carry current, except during a fault condition (and we hope there aren't 2 independent fault conditions occurring at once).
However, current flows in loops. Neutral is the normal "return half" of the loop, and it needs to be dedicated to this circuit. In fact, neutrals don't have fuses and rely on the circuit breaker on the hot side to protect the neutral. You can't have two circuits sharing a neutral, or you get this!
But there's another problem. This is AC power. It reverses polarity 100/120 times a second, which throws electro-magnetic force into everything around the wires. That's why transformers work. To keep that from causing a lot of problems, we require that all the current that goes out one wire comes back on another in the same cable or conduit. Among the wires, currents are equal and opposite, so their electro-magnetic forces cancel each other out.
Now, borrowing a neutral means current is now making a big loop - "out" (really, it's AC) this circuit's "hot" wire and returning via another circuit's "neutral" wire. That will throw EMF on both circuits, causing all sorts of mischief - eddy current heating, wire vibration leading to noise and metal fatigue leading to cracking and spot heating, etc. Nope.
Because of this, all practical wiring is done on a physical "tree" topology -- a branch may "split", but it may never "loop back" onto itself or another branch (except in one particular way, and even then, only in the UK where this is officially sanctioned).
Now, it can be hard to see when you're not practiced in a field. But this is most likely an easy problem. Wire breaks inside walls are rare. Wire problems are almost always at terminations of the cable run... And by definition, this must occur at either the last working outlet or the first failed outlet in the sequence.
As Nate discusses in his answer, backstab connections are the usual culprit. You're best changing it to a screw connection, but current Code advises using an $80 torque screwdriver, because "too loose" is more of a problem than "too tight".
If it's at the service panel, the neutral may go to a neutral bar, or a GFCI or AFCI breaker. Torque matters here too.
Lastly, if this diagnosis is given you by a 3-light tester, know that some of us call it a "Magic 8-ball" tester. It is made as a pass-fail device for new wiring e.g. During new construction. When troubleshooting old existing work, the legends can be wrong to the point of whimsical. The lights are useful; they save you the trouble of making 3 measurements with a neon tester.
Absolutely not. That sort of thinking works with safety ground, which does not ever carry current, except during a fault condition (and we hope there aren't 2 independent fault conditions occurring at once).
However, current flows in loops. Neutral is the normal "return half" of the loop, and it needs to be dedicated to this circuit. In fact, neutrals don't have fuses and rely on the circuit breaker on the hot side to protect the neutral. You can't have two circuits sharing a neutral, or you get this!
But there's another problem. This is AC power. It reverses polarity 100/120 times a second, which throws electro-magnetic force into everything around the wires. That's why transformers work. To keep that from causing a lot of problems, we require that all the current that goes out one wire comes back on another in the same cable or conduit. Among the wires, currents are equal and opposite, so their electro-magnetic forces cancel each other out.
Now, borrowing a neutral means current is now making a big loop - "out" (really, it's AC) this circuit's "hot" wire and returning via another circuit's "neutral" wire. That will throw EMF on both circuits, causing all sorts of mischief - eddy current heating, wire vibration leading to noise and metal fatigue leading to cracking and spot heating, etc. Nope.
Because of this, all practical wiring is done on a physical "tree" topology -- a branch may "split", but it may never "loop back" onto itself or another branch (except in one particular way, and even then, only in the UK where this is officially sanctioned).
Now, it can be hard to see when you're not practiced in a field. But this is most likely an easy problem. Wire breaks inside walls are rare. Wire problems are almost always at terminations of the cable run... And by definition, this must occur at either the last working outlet or the first failed outlet in the sequence.
As Nate discusses in his answer, backstab connections are the usual culprit. You're best changing it to a screw connection, but current Code advises using an $80 torque screwdriver, because "too loose" is more of a problem than "too tight".
If it's at the service panel, the neutral may go to a neutral bar, or a GFCI or AFCI breaker. Torque matters here too.
Lastly, if this diagnosis is given you by a 3-light tester, know that some of us call it a "Magic 8-ball" tester. It is made as a pass-fail device for new wiring e.g. During new construction. When troubleshooting old existing work, the legends can be wrong to the point of whimsical. The lights are useful; they save you the trouble of making 3 measurements with a neon tester.
edited 51 mins ago
answered 1 hour ago
HarperHarper
75.4k449151
75.4k449151
add a comment |
add a comment |
James Wolf is a new contributor. Be nice, and check out our Code of Conduct.
James Wolf is a new contributor. Be nice, and check out our Code of Conduct.
James Wolf is a new contributor. Be nice, and check out our Code of Conduct.
James Wolf is a new contributor. Be nice, and check out our Code of Conduct.
Thanks for contributing an answer to Home Improvement Stack Exchange!
- Please be sure to answer the question. Provide details and share your research!
But avoid …
- Asking for help, clarification, or responding to other answers.
- Making statements based on opinion; back them up with references or personal experience.
To learn more, see our tips on writing great answers.
Sign up or log in
StackExchange.ready(function ()
StackExchange.helpers.onClickDraftSave('#login-link');
);
Sign up using Google
Sign up using Facebook
Sign up using Email and Password
Post as a guest
Required, but never shown
StackExchange.ready(
function ()
StackExchange.openid.initPostLogin('.new-post-login', 'https%3a%2f%2fdiy.stackexchange.com%2fquestions%2f161304%2fcan-i-run-a-new-neutral-wire-to-repair-a-broken-circuit%23new-answer', 'question_page');
);
Post as a guest
Required, but never shown
Sign up or log in
StackExchange.ready(function ()
StackExchange.helpers.onClickDraftSave('#login-link');
);
Sign up using Google
Sign up using Facebook
Sign up using Email and Password
Post as a guest
Required, but never shown
Sign up or log in
StackExchange.ready(function ()
StackExchange.helpers.onClickDraftSave('#login-link');
);
Sign up using Google
Sign up using Facebook
Sign up using Email and Password
Post as a guest
Required, but never shown
Sign up or log in
StackExchange.ready(function ()
StackExchange.helpers.onClickDraftSave('#login-link');
);
Sign up using Google
Sign up using Facebook
Sign up using Email and Password
Sign up using Google
Sign up using Facebook
Sign up using Email and Password
Post as a guest
Required, but never shown
Required, but never shown
Required, but never shown
Required, but never shown
Required, but never shown
Required, but never shown
Required, but never shown
Required, but never shown
Required, but never shown