Using an older 200A breaker panel on a 60A feeder circuit from house?Grounding requirements for main panel and subpanelUsing a 100A main breaker in a 200A panelHow should I wire a subpanel for a tiny house?Loads for sub panels from 150A split-bus main panelHow do I wire up a shed for 60A service today with the ability to grow later?Best choice for sub-panel and circuits for basementcan I turn a spa panel box into a circuit breaker boxIs there is a Standard on how much main service panel / main circuit breaker amps should be?Adding subpanel to a shedCan a sub-panel have a larger main breaker than the feeder breaker in the main panel?

Multi tool use
Multi tool use

Does capillary rise violate hydrostatic paradox?

Taking the numerator and the denominator

Make a Bowl of Alphabet Soup

Can you take a "free object interaction" while incapacitated?

Air travel with refrigerated insulin

Error in master's thesis, I do not know what to do

Magnifying glass in hyperbolic space

Relations between homogeneous polynomials

Can you describe someone as luxurious? As in someone who likes luxurious things?

Highest stage count that are used one right after the other?

PTIJ: Which Dr. Seuss books should one obtain?

Checking @@ROWCOUNT failing

Did I make a mistake by ccing email to boss to others?

Hashing password to increase entropy

Pre-Employment Background Check With Consent For Future Checks

Put the phone down / Put down the phone

Started in 1987 vs. Starting in 1987

How to preserve electronics (computers, ipads, phones) for hundreds of years?

Why do Radio Buttons not fill the entire outer circle?

Friend wants my recommendation but I don't want to give it to him

Asserting that Atheism and Theism are both faith based positions

Why is implicit conversion not ambiguous for non-primitive types?

Has the laser at Magurele, Romania reached a tenth of the Sun's power?

Why is indicated airspeed rather than ground speed used during the takeoff roll?



Using an older 200A breaker panel on a 60A feeder circuit from house?


Grounding requirements for main panel and subpanelUsing a 100A main breaker in a 200A panelHow should I wire a subpanel for a tiny house?Loads for sub panels from 150A split-bus main panelHow do I wire up a shed for 60A service today with the ability to grow later?Best choice for sub-panel and circuits for basementcan I turn a spa panel box into a circuit breaker boxIs there is a Standard on how much main service panel / main circuit breaker amps should be?Adding subpanel to a shedCan a sub-panel have a larger main breaker than the feeder breaker in the main panel?













1















I'm in the planning stages of a new workshop/shed build. I plan to run a 60A ciruit from the main panel in the house to a subpanel in the shed.



I recently picked up a used Challenger QM322200 200A breaker panel with about a dozen circuit breakers for a song. Can I use this panel as is, with the stock 200A main breaker as a master shut-off? (I'd relabel the panel as 60A).



If no, where can I find a 60A main breaker to swap into the panel?



Thanks for your help.










share|improve this question







New contributor




Charles Lemon is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.




















  • Harper or one of the other pros will provide more detail, but there are apparently problems with some Challenger breakers. So it may have been cheap because it was somebody's extra, or it may have been cheap because it was junk. List the type of breakers or post a picture and I'm sure the pros can let you know. As far as 200A vs. 60A, assuming there is a 60A breaker in the main panel for the feed to the subpanel, then you can have any size subpanel because the main breaker is a shutoff switch and not needed as an actual safety breaker.

    – manassehkatz
    4 hours ago











  • The panel was a working pull from a renovation - they homeowner upgraded the panel for more circuits. As far as I know, there is no problem with the panel as such. It's not the newest tech, but it all seems solid enough. The panel uses bolt-on BQL type breakers.

    – Charles Lemon
    4 hours ago











  • Also keep in mind that since you are doing new work, you may need to have AFCI and/or GFCI protection for various circuits.

    – manassehkatz
    4 hours ago






  • 1





    Yep - If I need to buy a few new breakers, that's fine.

    – Charles Lemon
    4 hours ago






  • 1





    @manassehkatz On panels and breakers, ThreePhaseEel is the expert, and just knows this stuff, or has access to all the right resources. Anything I know I learned from TPE.

    – Harper
    1 hour ago
















1















I'm in the planning stages of a new workshop/shed build. I plan to run a 60A ciruit from the main panel in the house to a subpanel in the shed.



I recently picked up a used Challenger QM322200 200A breaker panel with about a dozen circuit breakers for a song. Can I use this panel as is, with the stock 200A main breaker as a master shut-off? (I'd relabel the panel as 60A).



If no, where can I find a 60A main breaker to swap into the panel?



Thanks for your help.










share|improve this question







New contributor




Charles Lemon is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.




















  • Harper or one of the other pros will provide more detail, but there are apparently problems with some Challenger breakers. So it may have been cheap because it was somebody's extra, or it may have been cheap because it was junk. List the type of breakers or post a picture and I'm sure the pros can let you know. As far as 200A vs. 60A, assuming there is a 60A breaker in the main panel for the feed to the subpanel, then you can have any size subpanel because the main breaker is a shutoff switch and not needed as an actual safety breaker.

    – manassehkatz
    4 hours ago











  • The panel was a working pull from a renovation - they homeowner upgraded the panel for more circuits. As far as I know, there is no problem with the panel as such. It's not the newest tech, but it all seems solid enough. The panel uses bolt-on BQL type breakers.

    – Charles Lemon
    4 hours ago











  • Also keep in mind that since you are doing new work, you may need to have AFCI and/or GFCI protection for various circuits.

    – manassehkatz
    4 hours ago






  • 1





    Yep - If I need to buy a few new breakers, that's fine.

    – Charles Lemon
    4 hours ago






  • 1





    @manassehkatz On panels and breakers, ThreePhaseEel is the expert, and just knows this stuff, or has access to all the right resources. Anything I know I learned from TPE.

    – Harper
    1 hour ago














1












1








1








I'm in the planning stages of a new workshop/shed build. I plan to run a 60A ciruit from the main panel in the house to a subpanel in the shed.



I recently picked up a used Challenger QM322200 200A breaker panel with about a dozen circuit breakers for a song. Can I use this panel as is, with the stock 200A main breaker as a master shut-off? (I'd relabel the panel as 60A).



If no, where can I find a 60A main breaker to swap into the panel?



Thanks for your help.










share|improve this question







New contributor




Charles Lemon is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.












I'm in the planning stages of a new workshop/shed build. I plan to run a 60A ciruit from the main panel in the house to a subpanel in the shed.



I recently picked up a used Challenger QM322200 200A breaker panel with about a dozen circuit breakers for a song. Can I use this panel as is, with the stock 200A main breaker as a master shut-off? (I'd relabel the panel as 60A).



If no, where can I find a 60A main breaker to swap into the panel?



Thanks for your help.







circuit-breaker subpanel






share|improve this question







New contributor




Charles Lemon is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.











share|improve this question







New contributor




Charles Lemon is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.









share|improve this question




share|improve this question






New contributor




Charles Lemon is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.









asked 4 hours ago









Charles LemonCharles Lemon

62




62




New contributor




Charles Lemon is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.





New contributor





Charles Lemon is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.






Charles Lemon is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.












  • Harper or one of the other pros will provide more detail, but there are apparently problems with some Challenger breakers. So it may have been cheap because it was somebody's extra, or it may have been cheap because it was junk. List the type of breakers or post a picture and I'm sure the pros can let you know. As far as 200A vs. 60A, assuming there is a 60A breaker in the main panel for the feed to the subpanel, then you can have any size subpanel because the main breaker is a shutoff switch and not needed as an actual safety breaker.

    – manassehkatz
    4 hours ago











  • The panel was a working pull from a renovation - they homeowner upgraded the panel for more circuits. As far as I know, there is no problem with the panel as such. It's not the newest tech, but it all seems solid enough. The panel uses bolt-on BQL type breakers.

    – Charles Lemon
    4 hours ago











  • Also keep in mind that since you are doing new work, you may need to have AFCI and/or GFCI protection for various circuits.

    – manassehkatz
    4 hours ago






  • 1





    Yep - If I need to buy a few new breakers, that's fine.

    – Charles Lemon
    4 hours ago






  • 1





    @manassehkatz On panels and breakers, ThreePhaseEel is the expert, and just knows this stuff, or has access to all the right resources. Anything I know I learned from TPE.

    – Harper
    1 hour ago


















  • Harper or one of the other pros will provide more detail, but there are apparently problems with some Challenger breakers. So it may have been cheap because it was somebody's extra, or it may have been cheap because it was junk. List the type of breakers or post a picture and I'm sure the pros can let you know. As far as 200A vs. 60A, assuming there is a 60A breaker in the main panel for the feed to the subpanel, then you can have any size subpanel because the main breaker is a shutoff switch and not needed as an actual safety breaker.

    – manassehkatz
    4 hours ago











  • The panel was a working pull from a renovation - they homeowner upgraded the panel for more circuits. As far as I know, there is no problem with the panel as such. It's not the newest tech, but it all seems solid enough. The panel uses bolt-on BQL type breakers.

    – Charles Lemon
    4 hours ago











  • Also keep in mind that since you are doing new work, you may need to have AFCI and/or GFCI protection for various circuits.

    – manassehkatz
    4 hours ago






  • 1





    Yep - If I need to buy a few new breakers, that's fine.

    – Charles Lemon
    4 hours ago






  • 1





    @manassehkatz On panels and breakers, ThreePhaseEel is the expert, and just knows this stuff, or has access to all the right resources. Anything I know I learned from TPE.

    – Harper
    1 hour ago

















Harper or one of the other pros will provide more detail, but there are apparently problems with some Challenger breakers. So it may have been cheap because it was somebody's extra, or it may have been cheap because it was junk. List the type of breakers or post a picture and I'm sure the pros can let you know. As far as 200A vs. 60A, assuming there is a 60A breaker in the main panel for the feed to the subpanel, then you can have any size subpanel because the main breaker is a shutoff switch and not needed as an actual safety breaker.

– manassehkatz
4 hours ago





Harper or one of the other pros will provide more detail, but there are apparently problems with some Challenger breakers. So it may have been cheap because it was somebody's extra, or it may have been cheap because it was junk. List the type of breakers or post a picture and I'm sure the pros can let you know. As far as 200A vs. 60A, assuming there is a 60A breaker in the main panel for the feed to the subpanel, then you can have any size subpanel because the main breaker is a shutoff switch and not needed as an actual safety breaker.

– manassehkatz
4 hours ago













The panel was a working pull from a renovation - they homeowner upgraded the panel for more circuits. As far as I know, there is no problem with the panel as such. It's not the newest tech, but it all seems solid enough. The panel uses bolt-on BQL type breakers.

– Charles Lemon
4 hours ago





The panel was a working pull from a renovation - they homeowner upgraded the panel for more circuits. As far as I know, there is no problem with the panel as such. It's not the newest tech, but it all seems solid enough. The panel uses bolt-on BQL type breakers.

– Charles Lemon
4 hours ago













Also keep in mind that since you are doing new work, you may need to have AFCI and/or GFCI protection for various circuits.

– manassehkatz
4 hours ago





Also keep in mind that since you are doing new work, you may need to have AFCI and/or GFCI protection for various circuits.

– manassehkatz
4 hours ago




1




1





Yep - If I need to buy a few new breakers, that's fine.

– Charles Lemon
4 hours ago





Yep - If I need to buy a few new breakers, that's fine.

– Charles Lemon
4 hours ago




1




1





@manassehkatz On panels and breakers, ThreePhaseEel is the expert, and just knows this stuff, or has access to all the right resources. Anything I know I learned from TPE.

– Harper
1 hour ago






@manassehkatz On panels and breakers, ThreePhaseEel is the expert, and just knows this stuff, or has access to all the right resources. Anything I know I learned from TPE.

– Harper
1 hour ago











1 Answer
1






active

oldest

votes


















4














You can use the 200 amp main as a disconnect it is fine since you will be using a 60 amp breaker in the main panel the wire needs to be sized for 60 amps. As long as the panel is as large as the service panel breaker or larger it would be code compliant.






share|improve this answer






















    Your Answer








    StackExchange.ready(function()
    var channelOptions =
    tags: "".split(" "),
    id: "73"
    ;
    initTagRenderer("".split(" "), "".split(" "), channelOptions);

    StackExchange.using("externalEditor", function()
    // Have to fire editor after snippets, if snippets enabled
    if (StackExchange.settings.snippets.snippetsEnabled)
    StackExchange.using("snippets", function()
    createEditor();
    );

    else
    createEditor();

    );

    function createEditor()
    StackExchange.prepareEditor(
    heartbeatType: 'answer',
    autoActivateHeartbeat: false,
    convertImagesToLinks: false,
    noModals: true,
    showLowRepImageUploadWarning: true,
    reputationToPostImages: null,
    bindNavPrevention: true,
    postfix: "",
    imageUploader:
    brandingHtml: "Powered by u003ca class="icon-imgur-white" href="https://imgur.com/"u003eu003c/au003e",
    contentPolicyHtml: "User contributions licensed under u003ca href="https://creativecommons.org/licenses/by-sa/3.0/"u003ecc by-sa 3.0 with attribution requiredu003c/au003e u003ca href="https://stackoverflow.com/legal/content-policy"u003e(content policy)u003c/au003e",
    allowUrls: true
    ,
    noCode: true, onDemand: true,
    discardSelector: ".discard-answer"
    ,immediatelyShowMarkdownHelp:true
    );



    );






    Charles Lemon is a new contributor. Be nice, and check out our Code of Conduct.









    draft saved

    draft discarded


















    StackExchange.ready(
    function ()
    StackExchange.openid.initPostLogin('.new-post-login', 'https%3a%2f%2fdiy.stackexchange.com%2fquestions%2f160204%2fusing-an-older-200a-breaker-panel-on-a-60a-feeder-circuit-from-house%23new-answer', 'question_page');

    );

    Post as a guest















    Required, but never shown

























    1 Answer
    1






    active

    oldest

    votes








    1 Answer
    1






    active

    oldest

    votes









    active

    oldest

    votes






    active

    oldest

    votes









    4














    You can use the 200 amp main as a disconnect it is fine since you will be using a 60 amp breaker in the main panel the wire needs to be sized for 60 amps. As long as the panel is as large as the service panel breaker or larger it would be code compliant.






    share|improve this answer



























      4














      You can use the 200 amp main as a disconnect it is fine since you will be using a 60 amp breaker in the main panel the wire needs to be sized for 60 amps. As long as the panel is as large as the service panel breaker or larger it would be code compliant.






      share|improve this answer

























        4












        4








        4







        You can use the 200 amp main as a disconnect it is fine since you will be using a 60 amp breaker in the main panel the wire needs to be sized for 60 amps. As long as the panel is as large as the service panel breaker or larger it would be code compliant.






        share|improve this answer













        You can use the 200 amp main as a disconnect it is fine since you will be using a 60 amp breaker in the main panel the wire needs to be sized for 60 amps. As long as the panel is as large as the service panel breaker or larger it would be code compliant.







        share|improve this answer












        share|improve this answer



        share|improve this answer










        answered 4 hours ago









        Ed BealEd Beal

        34.2k12148




        34.2k12148




















            Charles Lemon is a new contributor. Be nice, and check out our Code of Conduct.









            draft saved

            draft discarded


















            Charles Lemon is a new contributor. Be nice, and check out our Code of Conduct.












            Charles Lemon is a new contributor. Be nice, and check out our Code of Conduct.











            Charles Lemon is a new contributor. Be nice, and check out our Code of Conduct.














            Thanks for contributing an answer to Home Improvement Stack Exchange!


            • Please be sure to answer the question. Provide details and share your research!

            But avoid


            • Asking for help, clarification, or responding to other answers.

            • Making statements based on opinion; back them up with references or personal experience.

            To learn more, see our tips on writing great answers.




            draft saved


            draft discarded














            StackExchange.ready(
            function ()
            StackExchange.openid.initPostLogin('.new-post-login', 'https%3a%2f%2fdiy.stackexchange.com%2fquestions%2f160204%2fusing-an-older-200a-breaker-panel-on-a-60a-feeder-circuit-from-house%23new-answer', 'question_page');

            );

            Post as a guest















            Required, but never shown





















































            Required, but never shown














            Required, but never shown












            Required, but never shown







            Required, but never shown

































            Required, but never shown














            Required, but never shown












            Required, but never shown







            Required, but never shown







            b9MNqDt3bK EbfRW6RwFkkEKe,pp7YpUqhb79
            N9XZFMN6fJl,8F89M,4ydiodXLWQivkLR8C ajd,wQBZ9 UQSCd 73Nf EO6G BJ0JVre0 Sv LKDiSMWOpssO

            Popular posts from this blog

            Creating centerline of river in QGIS? The 2019 Stack Overflow Developer Survey Results Are In Announcing the arrival of Valued Associate #679: Cesar Manara Planned maintenance scheduled April 17/18, 2019 at 00:00UTC (8:00pm US/Eastern)Finding centrelines from polygons in QGIS?Splitting line into two lines with GRASS GIS?Centroid of the equator and a pointpostgis: problems creating flow direction polyline; not all needed connections are drawnhow to make decent sense from scattered river depth measurementsQGIS Interpolation on Curved Grid (River DEMs)How to create automatic parking baysShortest path creation between two linesclipping layer using query builder in QGISFinding which side of closest polyline point lies on in QGIS?Create centerline from multi-digitized roadway lines Qgis 2.18Getting bathymetric contours confined only within river banks using QGIS?

            What is the result of assigning to std::vector::begin()? The Next CEO of Stack OverflowWhat are the differences between a pointer variable and a reference variable in C++?What does the explicit keyword mean?Concatenating two std::vectorsHow to find out if an item is present in a std::vector?Why is “using namespace std” considered bad practice?What is the “-->” operator in C++?What is the easiest way to initialize a std::vector with hardcoded elements?What is The Rule of Three?What are the basic rules and idioms for operator overloading?Why are std::begin and std::end “not memory safe”?